tef.eu ‑ globalfire.pt Manufacturers of Fire Detection Equipment TEF‑GFE ‑ 2023 TECHNICAL SPECIFICATIONS POWER SUPPLY MAINS SUPPLY VOLTAGE 230 +10% ‑15% V AC INTERNAL POWER SUPPLY Min. 21V DC ‑ Max. 30V DC (28.5V DC nominal) Max. Ripple 1 Vpp TOTAL OUTPUT CURRENT 1,7A @ 230V AC MONITORED SUPPLY & BATTERY CHARGER Yes MONITORED BATTERIES Yes BATTERIES MAX. INTERNAL RESISTANCE 1 Ohm MAX BATTERY SIZE 2 x 12V 7AH VRLA ‑ Sealed Lead Acid Batteries Min. Voltage 21,0V DC (Vb min) ‑ Max. Voltage 27,2V DC MAINS FUSE 4 A ‑ 250V Slow Blow ‑ 20 mm BATTERY FUSE 1.6 Amp Resettable ‑ Electronic Fuse MAX CURRENT DRAW FROM BATTERY (MAINS FAILURE) 1.5 Amp Max. @ Max. Operating Temperature SOUNDER CIRCUIT NUMBER OF CIRCUITS 1 END OF LINE RESISTOR VALUE 10K Ohms MONITORING Open and Short Circuit ALARM VOLTAGE 27.5V DC SOUNDER CIRCUIT FUSE 1.1 Amp resettable (Electronic Fuse) MAX. CURRENT AVAILABLE 900 mA @ 27.5V DC Nominal AUXILIARY OUTPUTS DC POWER OUTPUT 27.5V DC Nominal ‑ Max. Current Drawn 900 mA FIRE RELAY Active in Fire condition, 2A @ 30V DC resistive / 0.25A @ 230V AC resistive; SPDT FAULT RELAY Active in Fault condition, 2A @ 30V DC resistive / 0.25A @ 230V AC resistive; NC DIMENSIONS SIZE 273 (L) x 107 (W) x 404 (H) mm WEIGHT 1,7 Kg / 7 kg (inc. 2 x 7 AH 12 V batteries) OPERATING TEMPERATURE ‑10 to +50ºC MAX RELATIVE HUMIDITY 95% non condensing ADDRESSABLE LOOP INTERFACE SUPPLY VOLTAGE 17 V to 30V DC SUPPLY CURRENT 1.2 mA Quiescent ‑ 3 mA Alarm or Fault ORDER CODE ADLI‑BCM LSC ADDRESSABLE MODULE w/INTEGRATED LOOP SOUNDER CIRCUIT (LSC) ORION‑BCM 1328‑CPR‑0537 BATTERY/CHARGER MODULE w/INTEGRATED SOUNDER CIRCUIT