+31 (0)180 554555 sales@tef.eu

Archives

10nov2013

What is the maximum length for a detection loop in a GFE analog panel?

  • By ivo
  • 0 Tags
  • 0 Comments
The maximum recommended length is approximately 1200 m, but this value depends largely on the cable cross section and the load of the devices in that loop. We developed the GFE Loop Calculator software where it is possible to verify if your system has an appropriate loop length.
10nov2013

Which cable cross section is recommended to the detection loops?

  • By ivo
  • 0 Tags
  • 0 Comments
You should always use shielded cable of the type appropriate for fire detection installations. Please note that cable types are also regulated by local authorities/ standards. As a rule of thumb you should use: a) 0,8 mm2 for loop lengths up to 500 m b) 1.0 mm2 for loop lengths up to 800 m c) 1.5 mm2 for
?>